Lead time | Usually Ships within 2 Weeks |
Main Input Voltage | 400 V 3 phases |
Other Input Voltage | 380 V 415 V |
Main Output Voltage | 400 V 3 phases |
Other Output Voltage | 380 V 415 V |
rated power in W | 180 kW |
Rated power in VA | 200 kVA |
Output connector type | Hard wire 4-wire (3P + E) 1 Hard wire 5-wire (3P + N + E) 1 |
Battery type | External battery system |
Provided equipment | Built-in modbus protocol adapter Dust filter Installation guide Integrated network management Seismic compliance Top and bottom cable entry |
Number of battery filled slots | 0 |
Battery voltage | 480 V |
Discharge battery voltage | 384 V |
Max current discharge | 393 A |
Battery power in VAH | 0 VAh runtime |
Extended runtime | 0 |
Bypass voltage tolerance | +/- 10 % settable from +/- 4/6/8 and 10 % |
Max bypass input current | 289 A |
Bypass current protection | 400 A |
Redundant | No |
Colour | White |
Height | 197 cm |
Width | 105.2 cm |
Depth | 85.4 cm |
Product weight | 724 kg |
USB compatible | No |
Network frequency | 40...70 Hz |
Input voltage limits | 250...600 V adjustable 320...456 V 380 V 320...480 V 400 V 320...498 V 415 V |
Maximum input current | 328 A |
Switching current capacity | 400 A |
Max short time withstand current | 65 kA |
Input harmonic distortion | Less than 3 % for full load |
Input protection type | GL fuse |
Inrush current | 200 A peak |
Load power factor | 0.5 leading to 0.5 lagging |
Input Power Factor at Full Load | 1 |
Maximum configurable power in W | 180 kW |
Harmonic distortion | Less than 2 % |
Output frequency | 50/60 Hz +/- 1 Hz sync to mains 50/60 Hz +/- 1 Hz unsynchronised |
Crest factor | Unlimited |
Wave type | Sine wave |
Output voltage tolerance | +/- 1% static and +/- 3% at 100% load step |
Output harmonic distortion | < 2% linear load and < 3% non-linear load |
Output overload operation | 10 minutes at 125% and 60 seconds at 150% |
Neutral output current | 289 A |
bypass type | Built-in static bypass |
Maximum configurable power in VA | 200 kVA |
Product certifications | C-Tick CE RCM |
standards | EN/IEC 62040-1 EN/IEC 62040-2 EN/IEC 62040-3 IBC 2012 and CBC2013 to Sds=2.02g ISTA 2B OSHPD UL 1778 |
Ambient air temperature for operation | 0…40 °C |
Relative humidity | 0…95 % |
Operating altitude | 0...3333 ft |
Ambient air temperature for storage | -25…55 °C |
Storage Relative Humidity | 0…95 % |
Storage altitude | 0.00…14999.82 m |
Acoustic level | 65 dBA |
Heat dissipation | 24570 Btu/h |
IP degree of protection | IP20 |
Free slots | 2 |
Control panel | 7 touch screen display |
Emergency power off | Yes |
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 215.6 cm |
Package 1 Width | 106 cm |
Package 1 Length | 149 cm |
Package 1 Weight | 770 kg |
Warranty | 1 year on-site repair or replace with factory authorized Start-Up |